thermal: sysfs-api.txt - reformat for improved readability
The document currently uses large indentations which make the text too wide for easy readability. Also improve general consistency. Signed-off-by: Frans Pop <elendil@planet.nl> Acked-by: Zhang Rui <rui.zhang@intel.com> Signed-off-by: Andrew Morton <akpm@linux-foundation.org> Signed-off-by: Len Brown <len.brown@intel.com>
This commit is contained in:
parent
625120a42b
commit
38bb0849a6
|
@ -1,5 +1,5 @@
|
|||
Generic Thermal Sysfs driver How To
|
||||
=========================
|
||||
===================================
|
||||
|
||||
Written by Sujith Thomas <sujith.thomas@intel.com>, Zhang Rui <rui.zhang@intel.com>
|
||||
|
||||
|
@ -10,20 +10,20 @@ Copyright (c) 2008 Intel Corporation
|
|||
|
||||
0. Introduction
|
||||
|
||||
The generic thermal sysfs provides a set of interfaces for thermal zone devices (sensors)
|
||||
and thermal cooling devices (fan, processor...) to register with the thermal management
|
||||
solution and to be a part of it.
|
||||
The generic thermal sysfs provides a set of interfaces for thermal zone
|
||||
devices (sensors) and thermal cooling devices (fan, processor...) to register
|
||||
with the thermal management solution and to be a part of it.
|
||||
|
||||
This how-to focuses on enabling new thermal zone and cooling devices to participate
|
||||
in thermal management.
|
||||
This solution is platform independent and any type of thermal zone devices and
|
||||
cooling devices should be able to make use of the infrastructure.
|
||||
This how-to focuses on enabling new thermal zone and cooling devices to
|
||||
participate in thermal management.
|
||||
This solution is platform independent and any type of thermal zone devices
|
||||
and cooling devices should be able to make use of the infrastructure.
|
||||
|
||||
The main task of the thermal sysfs driver is to expose thermal zone attributes as well
|
||||
as cooling device attributes to the user space.
|
||||
An intelligent thermal management application can make decisions based on inputs
|
||||
from thermal zone attributes (the current temperature and trip point temperature)
|
||||
and throttle appropriate devices.
|
||||
The main task of the thermal sysfs driver is to expose thermal zone attributes
|
||||
as well as cooling device attributes to the user space.
|
||||
An intelligent thermal management application can make decisions based on
|
||||
inputs from thermal zone attributes (the current temperature and trip point
|
||||
temperature) and throttle appropriate devices.
|
||||
|
||||
[0-*] denotes any positive number starting from 0
|
||||
[1-*] denotes any positive number starting from 1
|
||||
|
@ -31,77 +31,77 @@ and throttle appropriate devices.
|
|||
1. thermal sysfs driver interface functions
|
||||
|
||||
1.1 thermal zone device interface
|
||||
1.1.1 struct thermal_zone_device *thermal_zone_device_register(char *name, int trips,
|
||||
void *devdata, struct thermal_zone_device_ops *ops)
|
||||
1.1.1 struct thermal_zone_device *thermal_zone_device_register(char *name,
|
||||
int trips, void *devdata, struct thermal_zone_device_ops *ops)
|
||||
|
||||
This interface function adds a new thermal zone device (sensor) to
|
||||
/sys/class/thermal folder as thermal_zone[0-*].
|
||||
It tries to bind all the thermal cooling devices registered at the same time.
|
||||
This interface function adds a new thermal zone device (sensor) to
|
||||
/sys/class/thermal folder as thermal_zone[0-*]. It tries to bind all the
|
||||
thermal cooling devices registered at the same time.
|
||||
|
||||
name: the thermal zone name.
|
||||
trips: the total number of trip points this thermal zone supports.
|
||||
devdata: device private data
|
||||
ops: thermal zone device call-backs.
|
||||
.bind: bind the thermal zone device with a thermal cooling device.
|
||||
.unbind: unbind the thermal zone device with a thermal cooling device.
|
||||
.get_temp: get the current temperature of the thermal zone.
|
||||
.get_mode: get the current mode (user/kernel) of the thermal zone.
|
||||
"kernel" means thermal management is done in kernel.
|
||||
"user" will prevent kernel thermal driver actions upon trip points
|
||||
so that user applications can take charge of thermal management.
|
||||
.set_mode: set the mode (user/kernel) of the thermal zone.
|
||||
.get_trip_type: get the type of certain trip point.
|
||||
.get_trip_temp: get the temperature above which the certain trip point
|
||||
will be fired.
|
||||
name: the thermal zone name.
|
||||
trips: the total number of trip points this thermal zone supports.
|
||||
devdata: device private data
|
||||
ops: thermal zone device call-backs.
|
||||
.bind: bind the thermal zone device with a thermal cooling device.
|
||||
.unbind: unbind the thermal zone device with a thermal cooling device.
|
||||
.get_temp: get the current temperature of the thermal zone.
|
||||
.get_mode: get the current mode (user/kernel) of the thermal zone.
|
||||
- "kernel" means thermal management is done in kernel.
|
||||
- "user" will prevent kernel thermal driver actions upon trip points
|
||||
so that user applications can take charge of thermal management.
|
||||
.set_mode: set the mode (user/kernel) of the thermal zone.
|
||||
.get_trip_type: get the type of certain trip point.
|
||||
.get_trip_temp: get the temperature above which the certain trip point
|
||||
will be fired.
|
||||
|
||||
1.1.2 void thermal_zone_device_unregister(struct thermal_zone_device *tz)
|
||||
|
||||
This interface function removes the thermal zone device.
|
||||
It deletes the corresponding entry form /sys/class/thermal folder and unbind all
|
||||
the thermal cooling devices it uses.
|
||||
This interface function removes the thermal zone device.
|
||||
It deletes the corresponding entry form /sys/class/thermal folder and
|
||||
unbind all the thermal cooling devices it uses.
|
||||
|
||||
1.2 thermal cooling device interface
|
||||
1.2.1 struct thermal_cooling_device *thermal_cooling_device_register(char *name,
|
||||
void *devdata, struct thermal_cooling_device_ops *)
|
||||
void *devdata, struct thermal_cooling_device_ops *)
|
||||
|
||||
This interface function adds a new thermal cooling device (fan/processor/...) to
|
||||
/sys/class/thermal/ folder as cooling_device[0-*].
|
||||
It tries to bind itself to all the thermal zone devices register at the same time.
|
||||
name: the cooling device name.
|
||||
devdata: device private data.
|
||||
ops: thermal cooling devices call-backs.
|
||||
.get_max_state: get the Maximum throttle state of the cooling device.
|
||||
.get_cur_state: get the Current throttle state of the cooling device.
|
||||
.set_cur_state: set the Current throttle state of the cooling device.
|
||||
This interface function adds a new thermal cooling device (fan/processor/...)
|
||||
to /sys/class/thermal/ folder as cooling_device[0-*]. It tries to bind itself
|
||||
to all the thermal zone devices register at the same time.
|
||||
name: the cooling device name.
|
||||
devdata: device private data.
|
||||
ops: thermal cooling devices call-backs.
|
||||
.get_max_state: get the Maximum throttle state of the cooling device.
|
||||
.get_cur_state: get the Current throttle state of the cooling device.
|
||||
.set_cur_state: set the Current throttle state of the cooling device.
|
||||
|
||||
1.2.2 void thermal_cooling_device_unregister(struct thermal_cooling_device *cdev)
|
||||
|
||||
This interface function remove the thermal cooling device.
|
||||
It deletes the corresponding entry form /sys/class/thermal folder and unbind
|
||||
itself from all the thermal zone devices using it.
|
||||
This interface function remove the thermal cooling device.
|
||||
It deletes the corresponding entry form /sys/class/thermal folder and
|
||||
unbind itself from all the thermal zone devices using it.
|
||||
|
||||
1.3 interface for binding a thermal zone device with a thermal cooling device
|
||||
1.3.1 int thermal_zone_bind_cooling_device(struct thermal_zone_device *tz,
|
||||
int trip, struct thermal_cooling_device *cdev);
|
||||
int trip, struct thermal_cooling_device *cdev);
|
||||
|
||||
This interface function bind a thermal cooling device to the certain trip point
|
||||
of a thermal zone device.
|
||||
This function is usually called in the thermal zone device .bind callback.
|
||||
tz: the thermal zone device
|
||||
cdev: thermal cooling device
|
||||
trip: indicates which trip point the cooling devices is associated with
|
||||
in this thermal zone.
|
||||
This interface function bind a thermal cooling device to the certain trip
|
||||
point of a thermal zone device.
|
||||
This function is usually called in the thermal zone device .bind callback.
|
||||
tz: the thermal zone device
|
||||
cdev: thermal cooling device
|
||||
trip: indicates which trip point the cooling devices is associated with
|
||||
in this thermal zone.
|
||||
|
||||
1.3.2 int thermal_zone_unbind_cooling_device(struct thermal_zone_device *tz,
|
||||
int trip, struct thermal_cooling_device *cdev);
|
||||
int trip, struct thermal_cooling_device *cdev);
|
||||
|
||||
This interface function unbind a thermal cooling device from the certain trip point
|
||||
of a thermal zone device.
|
||||
This function is usually called in the thermal zone device .unbind callback.
|
||||
tz: the thermal zone device
|
||||
cdev: thermal cooling device
|
||||
trip: indicates which trip point the cooling devices is associated with
|
||||
in this thermal zone.
|
||||
This interface function unbind a thermal cooling device from the certain
|
||||
trip point of a thermal zone device. This function is usually called in
|
||||
the thermal zone device .unbind callback.
|
||||
tz: the thermal zone device
|
||||
cdev: thermal cooling device
|
||||
trip: indicates which trip point the cooling devices is associated with
|
||||
in this thermal zone.
|
||||
|
||||
2. sysfs attributes structure
|
||||
|
||||
|
@ -114,153 +114,157 @@ if hwmon is compiled in or built as a module.
|
|||
|
||||
Thermal zone device sys I/F, created once it's registered:
|
||||
/sys/class/thermal/thermal_zone[0-*]:
|
||||
|-----type: Type of the thermal zone
|
||||
|-----temp: Current temperature
|
||||
|-----mode: Working mode of the thermal zone
|
||||
|-----trip_point_[0-*]_temp: Trip point temperature
|
||||
|-----trip_point_[0-*]_type: Trip point type
|
||||
|---type: Type of the thermal zone
|
||||
|---temp: Current temperature
|
||||
|---mode: Working mode of the thermal zone
|
||||
|---trip_point_[0-*]_temp: Trip point temperature
|
||||
|---trip_point_[0-*]_type: Trip point type
|
||||
|
||||
Thermal cooling device sys I/F, created once it's registered:
|
||||
/sys/class/thermal/cooling_device[0-*]:
|
||||
|-----type : Type of the cooling device(processor/fan/...)
|
||||
|-----max_state: Maximum cooling state of the cooling device
|
||||
|-----cur_state: Current cooling state of the cooling device
|
||||
|---type: Type of the cooling device(processor/fan/...)
|
||||
|---max_state: Maximum cooling state of the cooling device
|
||||
|---cur_state: Current cooling state of the cooling device
|
||||
|
||||
|
||||
These two dynamic attributes are created/removed in pairs.
|
||||
They represent the relationship between a thermal zone and its associated cooling device.
|
||||
They are created/removed for each
|
||||
thermal_zone_bind_cooling_device/thermal_zone_unbind_cooling_device successful execution.
|
||||
Then next two dynamic attributes are created/removed in pairs. They represent
|
||||
the relationship between a thermal zone and its associated cooling device.
|
||||
They are created/removed for each successful execution of
|
||||
thermal_zone_bind_cooling_device/thermal_zone_unbind_cooling_device.
|
||||
|
||||
/sys/class/thermal/thermal_zone[0-*]
|
||||
|-----cdev[0-*]: The [0-*]th cooling device in the current thermal zone
|
||||
|-----cdev[0-*]_trip_point: Trip point that cdev[0-*] is associated with
|
||||
/sys/class/thermal/thermal_zone[0-*]:
|
||||
|---cdev[0-*]: [0-*]th cooling device in current thermal zone
|
||||
|---cdev[0-*]_trip_point: Trip point that cdev[0-*] is associated with
|
||||
|
||||
Besides the thermal zone device sysfs I/F and cooling device sysfs I/F,
|
||||
the generic thermal driver also creates a hwmon sysfs I/F for each _type_ of
|
||||
thermal zone device. E.g. the generic thermal driver registers one hwmon class device
|
||||
and build the associated hwmon sysfs I/F for all the registered ACPI thermal zones.
|
||||
the generic thermal driver also creates a hwmon sysfs I/F for each _type_
|
||||
of thermal zone device. E.g. the generic thermal driver registers one hwmon
|
||||
class device and build the associated hwmon sysfs I/F for all the registered
|
||||
ACPI thermal zones.
|
||||
|
||||
/sys/class/hwmon/hwmon[0-*]:
|
||||
|-----name: The type of the thermal zone devices.
|
||||
|-----temp[1-*]_input: The current temperature of thermal zone [1-*].
|
||||
|-----temp[1-*]_critical: The critical trip point of thermal zone [1-*].
|
||||
|---name: The type of the thermal zone devices
|
||||
|---temp[1-*]_input: The current temperature of thermal zone [1-*]
|
||||
|---temp[1-*]_critical: The critical trip point of thermal zone [1-*]
|
||||
|
||||
Please read Documentation/hwmon/sysfs-interface for additional information.
|
||||
|
||||
***************************
|
||||
* Thermal zone attributes *
|
||||
***************************
|
||||
|
||||
type Strings which represent the thermal zone type.
|
||||
This is given by thermal zone driver as part of registration.
|
||||
Eg: "acpitz" indicates it's an ACPI thermal device.
|
||||
In order to keep it consistent with hwmon sys attribute,
|
||||
this should be a short, lowercase string,
|
||||
not containing spaces nor dashes.
|
||||
RO
|
||||
Required
|
||||
type
|
||||
Strings which represent the thermal zone type.
|
||||
This is given by thermal zone driver as part of registration.
|
||||
E.g: "acpitz" indicates it's an ACPI thermal device.
|
||||
In order to keep it consistent with hwmon sys attribute; this should
|
||||
be a short, lowercase string, not containing spaces nor dashes.
|
||||
RO, Required
|
||||
|
||||
temp Current temperature as reported by thermal zone (sensor)
|
||||
Unit: millidegree Celsius
|
||||
RO
|
||||
Required
|
||||
temp
|
||||
Current temperature as reported by thermal zone (sensor).
|
||||
Unit: millidegree Celsius
|
||||
RO, Required
|
||||
|
||||
mode One of the predefined values in [kernel, user]
|
||||
This file gives information about the algorithm
|
||||
that is currently managing the thermal zone.
|
||||
It can be either default kernel based algorithm
|
||||
or user space application.
|
||||
RW
|
||||
Optional
|
||||
kernel = Thermal management in kernel thermal zone driver.
|
||||
user = Preventing kernel thermal zone driver actions upon
|
||||
trip points so that user application can take full
|
||||
charge of the thermal management.
|
||||
mode
|
||||
One of the predefined values in [kernel, user].
|
||||
This file gives information about the algorithm that is currently
|
||||
managing the thermal zone. It can be either default kernel based
|
||||
algorithm or user space application.
|
||||
kernel = Thermal management in kernel thermal zone driver.
|
||||
user = Preventing kernel thermal zone driver actions upon
|
||||
trip points so that user application can take full
|
||||
charge of the thermal management.
|
||||
RW, Optional
|
||||
|
||||
trip_point_[0-*]_temp The temperature above which trip point will be fired
|
||||
Unit: millidegree Celsius
|
||||
RO
|
||||
Optional
|
||||
trip_point_[0-*]_temp
|
||||
The temperature above which trip point will be fired.
|
||||
Unit: millidegree Celsius
|
||||
RO, Optional
|
||||
|
||||
trip_point_[0-*]_type Strings which indicate the type of the trip point
|
||||
E.g. it can be one of critical, hot, passive,
|
||||
active[0-*] for ACPI thermal zone.
|
||||
RO
|
||||
Optional
|
||||
trip_point_[0-*]_type
|
||||
Strings which indicate the type of the trip point.
|
||||
E.g. it can be one of critical, hot, passive, active[0-*] for ACPI
|
||||
thermal zone.
|
||||
RO, Optional
|
||||
|
||||
cdev[0-*] Sysfs link to the thermal cooling device node where the sys I/F
|
||||
for cooling device throttling control represents.
|
||||
RO
|
||||
Optional
|
||||
cdev[0-*]
|
||||
Sysfs link to the thermal cooling device node where the sys I/F
|
||||
for cooling device throttling control represents.
|
||||
RO, Optional
|
||||
|
||||
cdev[0-*]_trip_point The trip point with which cdev[0-*] is associated in this thermal zone
|
||||
-1 means the cooling device is not associated with any trip point.
|
||||
RO
|
||||
Optional
|
||||
cdev[0-*]_trip_point
|
||||
The trip point with which cdev[0-*] is associated in this thermal
|
||||
zone; -1 means the cooling device is not associated with any trip
|
||||
point.
|
||||
RO, Optional
|
||||
|
||||
******************************
|
||||
* Cooling device attributes *
|
||||
******************************
|
||||
*****************************
|
||||
* Cooling device attributes *
|
||||
*****************************
|
||||
|
||||
type String which represents the type of device
|
||||
eg: For generic ACPI: this should be "Fan",
|
||||
"Processor" or "LCD"
|
||||
eg. For memory controller device on intel_menlow platform:
|
||||
this should be "Memory controller"
|
||||
RO
|
||||
Required
|
||||
type
|
||||
String which represents the type of device, e.g:
|
||||
- for generic ACPI: should be "Fan", "Processor" or "LCD"
|
||||
- for memory controller device on intel_menlow platform:
|
||||
should be "Memory controller".
|
||||
RO, Required
|
||||
|
||||
max_state The maximum permissible cooling state of this cooling device.
|
||||
RO
|
||||
Required
|
||||
max_state
|
||||
The maximum permissible cooling state of this cooling device.
|
||||
RO, Required
|
||||
|
||||
cur_state The current cooling state of this cooling device.
|
||||
the value can any integer numbers between 0 and max_state,
|
||||
cur_state == 0 means no cooling
|
||||
cur_state == max_state means the maximum cooling.
|
||||
RW
|
||||
Required
|
||||
cur_state
|
||||
The current cooling state of this cooling device.
|
||||
The value can any integer numbers between 0 and max_state:
|
||||
- cur_state == 0 means no cooling
|
||||
- cur_state == max_state means the maximum cooling.
|
||||
RW, Required
|
||||
|
||||
3. A simple implementation
|
||||
|
||||
ACPI thermal zone may support multiple trip points like critical/hot/passive/active.
|
||||
If an ACPI thermal zone supports critical, passive, active[0] and active[1] at the same time,
|
||||
it may register itself as a thermal_zone_device (thermal_zone1) with 4 trip points in all.
|
||||
It has one processor and one fan, which are both registered as thermal_cooling_device.
|
||||
If the processor is listed in _PSL method, and the fan is listed in _AL0 method,
|
||||
the sys I/F structure will be built like this:
|
||||
ACPI thermal zone may support multiple trip points like critical, hot,
|
||||
passive, active. If an ACPI thermal zone supports critical, passive,
|
||||
active[0] and active[1] at the same time, it may register itself as a
|
||||
thermal_zone_device (thermal_zone1) with 4 trip points in all.
|
||||
It has one processor and one fan, which are both registered as
|
||||
thermal_cooling_device.
|
||||
|
||||
If the processor is listed in _PSL method, and the fan is listed in _AL0
|
||||
method, the sys I/F structure will be built like this:
|
||||
|
||||
/sys/class/thermal:
|
||||
|
||||
|thermal_zone1:
|
||||
|-----type: acpitz
|
||||
|-----temp: 37000
|
||||
|-----mode: kernel
|
||||
|-----trip_point_0_temp: 100000
|
||||
|-----trip_point_0_type: critical
|
||||
|-----trip_point_1_temp: 80000
|
||||
|-----trip_point_1_type: passive
|
||||
|-----trip_point_2_temp: 70000
|
||||
|-----trip_point_2_type: active0
|
||||
|-----trip_point_3_temp: 60000
|
||||
|-----trip_point_3_type: active1
|
||||
|-----cdev0: --->/sys/class/thermal/cooling_device0
|
||||
|-----cdev0_trip_point: 1 /* cdev0 can be used for passive */
|
||||
|-----cdev1: --->/sys/class/thermal/cooling_device3
|
||||
|-----cdev1_trip_point: 2 /* cdev1 can be used for active[0]*/
|
||||
|---type: acpitz
|
||||
|---temp: 37000
|
||||
|---mode: kernel
|
||||
|---trip_point_0_temp: 100000
|
||||
|---trip_point_0_type: critical
|
||||
|---trip_point_1_temp: 80000
|
||||
|---trip_point_1_type: passive
|
||||
|---trip_point_2_temp: 70000
|
||||
|---trip_point_2_type: active0
|
||||
|---trip_point_3_temp: 60000
|
||||
|---trip_point_3_type: active1
|
||||
|---cdev0: --->/sys/class/thermal/cooling_device0
|
||||
|---cdev0_trip_point: 1 /* cdev0 can be used for passive */
|
||||
|---cdev1: --->/sys/class/thermal/cooling_device3
|
||||
|---cdev1_trip_point: 2 /* cdev1 can be used for active[0]*/
|
||||
|
||||
|cooling_device0:
|
||||
|-----type: Processor
|
||||
|-----max_state: 8
|
||||
|-----cur_state: 0
|
||||
|---type: Processor
|
||||
|---max_state: 8
|
||||
|---cur_state: 0
|
||||
|
||||
|cooling_device3:
|
||||
|-----type: Fan
|
||||
|-----max_state: 2
|
||||
|-----cur_state: 0
|
||||
|---type: Fan
|
||||
|---max_state: 2
|
||||
|---cur_state: 0
|
||||
|
||||
/sys/class/hwmon:
|
||||
|
||||
|hwmon0:
|
||||
|-----name: acpitz
|
||||
|-----temp1_input: 37000
|
||||
|-----temp1_crit: 100000
|
||||
|---name: acpitz
|
||||
|---temp1_input: 37000
|
||||
|---temp1_crit: 100000
|
||||
|
|
Loading…
Reference in New Issue