Kernel driver max16064
======================
Supported chips:
* Maxim MAX16064
Prefix: 'max16064'
Addresses scanned: -
Datasheet: http://datasheets.maxim-ic.com/en/ds/MAX16064.pdf
Author: Guenter Roeck <guenter.roeck@ericsson.com>
Description
-----------
This driver supports hardware montoring for Maxim MAX16064 Quad Power-Supply
Controller with Active-Voltage Output Control and PMBus Interface.
The driver is a client driver to the core PMBus driver.
Please see Documentation/hwmon/pmbus for details on PMBus client drivers.
Usage Notes
-----------
This driver does not auto-detect devices. You will have to instantiate the
devices explicitly. Please see Documentation/i2c/instantiating-devices for
details.
Platform data support
---------------------
The driver supports standard PMBus driver platform data.
Sysfs entries
-------------
The following attributes are supported. Limits are read-write; all other
attributes are read-only.
in[1-4]_label "vout[1-4]"
in[1-4]_input Measured voltage. From READ_VOUT register.
in[1-4]_min Minumum Voltage. From VOUT_UV_WARN_LIMIT register.
in[1-4]_max Maximum voltage. From VOUT_OV_WARN_LIMIT register.
in[1-4]_lcrit Critical minumum Voltage. VOUT_UV_FAULT_LIMIT register.
in[1-4]_crit Critical maximum voltage. From VOUT_OV_FAULT_LIMIT register.
in[1-4]_min_alarm Voltage low alarm. From VOLTAGE_UV_WARNING status.
in[1-4]_max_alarm Voltage high alarm. From VOLTAGE_OV_WARNING status.
in[1-4]_lcrit_alarm Voltage critical low alarm. From VOLTAGE_UV_FAULT status.
in[1-4]_crit_alarm Voltage critical high alarm. From VOLTAGE_OV_FAULT status.
temp1_input Measured temperature. From READ_TEMPERATURE_1 register.
temp1_max Maximum temperature. From OT_WARN_LIMIT register.
temp1_crit Critical high temperature. From OT_FAULT_LIMIT register.
temp1_max_alarm Chip temperature high alarm. Set by comparing
READ_TEMPERATURE_1 with OT_WARN_LIMIT if TEMP_OT_WARNING
status is set.
temp1_crit_alarm Chip temperature critical high alarm. Set by comparing
READ_TEMPERATURE_1 with OT_FAULT_LIMIT if TEMP_OT_FAULT
status is set.